| This page will outline our preferred specifications for use in datacenters.
| |
| | |
| | |
| This is summary data, and is not "live", any actual cable connections, and their cable color and labeling are tracked in [https://netbox.wikimedia.org/ Netbox].
| |
| | |
| == Cabling Specifications ==
| |
| {| class="wikitable"
| |
| |-
| |
| ! Color !! Cable Spec !! Network
| |
| |-
| |
| | Blue || Cat6 || Production
| |
| |-
| |
| | Green || Cat5e || Management
| |
| |-
| |
| | Orange || Cat5e || Serial
| |
| |-
| |
| | Red || Cat5e || Out of Band Access
| |
| |-
| |
| | Yellow || 9/125 Singlemode Fiber || All fiber connections
| |
| |}
| |
| | |
| * Fiber note: LC to LC in rack, SC to LC for peer/transit links.
| |
| * Cabling Notes:
| |
| :* We use pre-made patches in rack (5'/7'/10') for mgmt and production network.
| |
| :* We use custom on-site assembled patches for serial.
| |
| ::* These are nearly always cross-rack and must be custom measured.
| |
| ::* The pin out differs to work for serial console (cisco/juniper/netapp/sun) without an adapter:
| |
| :::* End Device Side: [[wikipedia:TIA/EIA-568#Wiring|568B]]
| |
| :::* Serial Console Side: pin 4 white-green, pin 5 green, pin 6 blue (remainder immaterial)
| |
| | |
| === Cabling Options ===
| |
| * Gear Mounted Top of Rack
| |
| :* 12 3M Fiber or 12 10' CAT6 Ethernet Cable
| |
| :* 24 2M Fiber or 24 7' CAT6 Ethernet Cable
| |
| :* 5 1M Fiber or 5 5' CAT6 Ethernet Cable
| |
| | |
| * Gear Mounted Mid-Rack
| |
| :* 10 1M Fiber or 10 5' CAT6 Ethernet Cable
| |
| :* 32 2M Fiber or 32 7' CAT6 Ethernet Cable
| |
| | |
| == Power Specifications ==
| |
| | |
| === CODFW & EQIAD Based Sites ===
| |
| * 208V 3 Phase power @ 30 Amps - Two circuits per enclosure for redundancy.
| |
| :* Sites in use: eqiad, sdtpa (not all racks redundant power)
| |
| :* Power connector used for 30AMP 3Phase is NEMA L21-30P(plug) / L21-30R(eceptacle).
| |
| ::* Sites not in use: pmtpa (208V 3 Phase @ 20 Amps, redundant) & ULSFO(redundant).
| |
| ::* Power connector used for 20AMP 3Phase is NEMA NEMA L21-20P(plug) / L21-20R(eceptacle).
| |
| | |
| * ServerTech 0U SMART PDU
| |
| * 42 c13 power ports per feed for a total of 84 ports.
| |
| :* Model: CS-84VDY-L2130
| |
| ::* Also have to order (2) EMTH-1-1 to have two temp/humidity leads, and one Kit-MB-01 (two button mount kit - can use Rittal equivalent)
| |
| :* In our present deployments, we use SMART over SWITCHED due to the higher possible rate of failure of the switched power ports over non-switched power ports.
| |
| :* We have a rack with switched power, due to legacy equipment that could not out of band power cycle; though now none of that hardware is still in service.
| |
| ::* RobH thinks we may need to re-investigate the failure rates on switched power, and possibly use it more, since it can be used to remotely clear service processors out of unrecoverable error states,
| |
| | |
| * Power cords for servers are c13/c14 type; with new cables being red or blue for A/B power feeds.
| |
| | |
| == Enclosure Specifications ==
| |
| === EQIAD Racks ===
| |
| * Depth from front rail to PDU (overall depth for hardware facing the front of the rack): 33"
| |
| * Rittal TS-8 Enclosure : Rittal 9962172
| |
| :* Sheet Steel, 800MM W by 2200MM H by 1050MM D. Sand Texture, Black, Perforated front/rear doors, standard rear wall/door, perforated with 4 round cable entry in roof.
| |
| :* We have to get three kinds, right side end of row, left side end of row, and enclosures within the row.
| |
| ::* Inner enclosure: partition wall left side : Right end enclosure: partition left, sidewall right :: Left end enclosure: sidewall left
| |
| | |
| * Rittal TS - External Baying Connector : Rittal 8800490 : One kit gangs together two enclosures
| |
| | |
| * Rittal Roof Mount Cable Manager for 32" Wide TS Enclosure : Rittal 9970016
| |
| | |
| * Rittal Button Mount Brackets
| |
| :* Rittal 9971067
| |
| === CODFW Racks ===
| |
| * Depth from front rail to PDU (overall depth for hardware facing the front of the rack): 38"
| |
| * Racksolutions racks purchased via CyrusOne.
| |
| | |
| === All other sites ===
| |
| * Racks are provided from the vendor in all other datacenter sites.
| |
| ** This section should still eventually list the "Depth from front rail to PDU (overall depth for hardware facing the front of the rack)" for each site.
| |
| | |
| == Serial Console ==
| |
| * Opengear CM7148 dual PSU model
| |
| :* 48 port serial console server
| |
| :* We attach serial to every power strip and every bit of network kit (excluding the rack level mgmt switches)
| |